| Stack Height of Diesel Generator Sets | ||
| For Generator Sets | Total Height of stack in Metre | |
| 50 KVA | Ht. of the building + 1.5 metre | |
| 50-100 KVA | Ht. of the building + 2.0 metre | |
| 100-150 KVA | Ht. of the building +2.5 metre | |
| 150-200 KVA | Ht. of the building + 3.0 metre | |
| 200-250 KVA | Ht. of the building + 3.5 metre | |
| 250-300 KVA | Ht. of the building + 3.5 metre | |
| Source : Environmental Standards for Ambient Air, Automobiles, | ||
| Fuels, Industries and Noise, Central Pollution Control Board, | ||
| Ministry of Environment & Forest. | ||